EXERGY ANALYSIS OF VAPOUR COMPRESSOR REFRIGERATION SYSTEM USING ALTERNATIVE REFRIGERANTS-A REVIEW
Author: Jyoti Soni, R.C. Gupta
Category: Technology
Abstract:The objective of this paper is to presents review on the exergy analysis of vapour compression
refrigeration system with using new refrigerants to replace CFCs and HCFCs. It is found that exergy analysis shows better and accurately location of inefficiency as compared to energy analysis. Exergy depends on the evaporator temperature, condenser temperature, degree of sub cooling and compressor pressure. The coefficient of performance (COP) and second law efficiency of the cycle increases, and exergy losses decreases with decreasing the emperature difference between the evaporator and refrigerated space and between condenser and outside air. It is also found that refrigerant should have low ODP and GWP. HC mixtures and R152a are the better substitutes to R12 in domestic refrigeration sector.R290, R1270, R290/R152a, R744 and HC/HFC mixtures are the long term substitutes for R22 in heat pump and in air conditioning system. In chiller application R11, R12 and R22 can be replaced by the R123
Keywords: COP, exergy losses, second law efficiency, sub cooling, new refrigerants
Full Text:
INTRODUCTION
The first vapour compression refrigeration cycle was developed in 1834. There are the various applications where vapour compression refrigeration system is used such as in air conditioning units, domestic refrigerator and chiller unit etc. In this system working fluid used is known as refrigerant which is the medium of heat transfer.
The first refrigerant used in vapour compression refrigeration system is sulfur dioxide which is highly flammable and toxic. In 1930 Freon group refrigerant was start in use in order to reduce the flammability and toxicity. The properties of refrigerants their life time in the atmosphere, the time required to ascent into the stratosphere their distribution in that atmosphere and chances of bombardment by high energy photons which will further destroyed the ozone layer. Even percentage of CFC‘s in the stratosphere is too small but their capacity to destroy O3layer is too large compared with CO2.Thier lifetime is also considerable so their warming effect may take a few decades or even a century.
Therefore, it is necessary to replace present conventional CFC refrigerants by some other refrigerants which will have less green house effect [17]. The commonly used refrigerants CFCs and HCFCs in many industrial and domestic applications are responsible to increase the ozone layer depletion and global warming. These refrigerants can be replaced by the new refrigerants such as R-134a, R-404a, R-407c, R-410a, R-290, and R-152a etc. and HC refrigerants which have zero ODP and low GWP in order to protect the environment [16]. The performance of the vapour compression refrigeration system can be calculated by two methods i.e. energy and exergy analysis. Energy analysis is based on the first law of the thermodynamic while exergy analysis based on the both first and second law of thermodynamic. The first law of the thermodynamic deals with quantity of energy and assert that energy cannot be created or destroyed, but it does not gives the information that how, where and how much the performance of the system degrade. Thus the second law of thermodynamic which deals with quality of energy is used to determine the performance degradation of the system. The second law of thermodynamic has proved to be a very powerful tool in the optimization of complex thermodynamic systems [8]. Basically in energy analysis calculate the work done by compressor (W), refrigerating effect ( ), power per ton refrigeration , volumetric refrigerating capacity (VCR) and coefficient of performance [2]. While exergy analysis discusses the exergy losses in each component of the system, exergy destruction ratio, efficiency defects, second law efficiency and also coefficient of performance . On the basis of the study it found is that exergy analysis shows better and accurately locations of inefficiency as compared to energy analysis. It is also found that exergy depend on the evaporator temperature, condenser temperature, degree of sub cooling and compressor pressure. The evaporating and condenser temperature have strong effects on the exergy losses of the evaporator and condenser, and on the second law efficiency and COP of the cycle but little effect on the exergy losses in the compressor and expansion valve. If the temperature difference between the evaporator and refrigerated space & between condenser and outside air is increased then the exergy losses is also increased and COP and second law efficiency decreased [3, 10]. This paper presents the review of the performance analysis of the vapour compression refrigeration system using various refrigerants which are the substitutes of CFCs and HCFCs. It is found that exergy analysis shows better and accurately locations of inefficiency as compared to energy analysis. Exergy depend on the evaporator temperature, condenser temperature, degree of sub cooling and compressor pressure. It is also shows that refrigerant should have low ODP and GWP. Thus the refrigerants R-134a, R-404a, R-407c, R-410a, R-290, and R-152a and HC blends are consider.
Description of Cycle
A simple vapour compression refrigeration system consists of four basic components illustrated via, evaporator, compressor, condenser and expansion valve. These components connected in a closed loop through piping that has heat transfer with the surrounding as shown in fig.1. At state 1, refrigerant leaves the evaporator at a low pressure, low temperature, saturated vapour and enter the compressor through the suction line in which both temperature and pressure increased. This process can be shown in fig.2. At state 2, it leaves the compressor as a high pressure, high temperature, superheated vapour and enter the condenser where it reject heat to surrounding medium at constant pressure after undergoing heat transfer in the discharge line. Refrigerant leaves the condenser at state 3, as high pressure, medium temperature, saturated liquid and enters the expansion valve. The expansion valve allows to flowing the high pressure liquid at constant enthalpy from high pressure to low pressure. At state 4, it leaves the expansion valve as a low temperature, low pressure, and liquid-vapour mixture and enters the evaporator where it absorbs the heat at constant pressure, changed into saturated vapour and cycle is completed.
Development of the System
As we know that COP and second law efficiency of the vapour compression refrigeration system can be increased by sub cooling. The sub cooling increases refrigerating capacity whereas there is no change in compressor work. As the COP of performance is the ratio of the refrigerating effect produced by evaporator to work done by compressor, hence COP increases. Vapour compression refrigeration cycle with liquid vapour heat exchanger including superheating and sub cooling as shown in fig.3.
From the analysis A.S. Dalkilic, S. Wongwises [2] shows that better performance obtained with sub cooling and superheating as compared to non sub cooling and non superheating condition. Akhilesh Arora, S.C. Kaushik [1] shows that exergy efficiency for 10 sub cooling is 14.9% for R404A and 14.8% for R507 at 40 condenser temperature and with decreasing the temperature differences between the evaporator and refrigerated space & between the condenser outside air COP and exergy efficiency increases, and exergy losses decreases.
LITERATURE REVIEW
Recep Yumrutas, Mehmet Kunduz, Mehmet Kanoglu [3] investigated the performance of the refrigeration system using NH3 as refrigerant based on the exergy analysis. It is found that the second law efficiency and COP increases & exergy losses decreases with decrease the temperature difference between evaporator and refrigerated space & between condenser and outside air. Arora and Kaushik [1] by using the computational model computing the coefficient of performance (COP), exergy destruction, Exergetic Efficiency and efficiency defects for R502, R404A and R507A. The evaporator and condenser temperature taken in the range of - 50 to 0 and 40 to 55 . The result indicates that R507A gives better performance as compared to R404A and R502A and it can be replace the R502 in future. A.S. Dalkilic, S. Wongwises [2] compare the performance of the vapour compression refrigeration system with consider the superheating and sub cooling conditions and using refrigerant mixture based on HFC134a, HFC152a, HFC32, HC290, HC1270, HC600 and HC600a in different ratios. Their result compared with the R12, R22 and R134a and finally it is concluded that all the alternative refrigerant have slightly lower coefficient as compared to R12, R22 and R134a but refrigerant blends of HC290/HC600a(40/60 by wt. %) can be replace R12 and HC290/HC1270(20/80 by wt. %) can be replace R22. B.O. Bolaji [12]proposed the of study of R152a and R32 to replace R134a in a domestic refrigerator by experiment and their result shows that R152a can be replace R134a in domestic refrigerator. Bilal Ahmed Qureshi, Syed M. Zubair [4] theoretically investigated the performance degradation of the refrigeration system due to fouling conditions in air side. There are two sets of refrigerants consider1st set include the refrigerant R134a, R410A and R407C and shows that 134a always performs better and 2nd set include the refrigerants R717, R404A and R290 and shows that R717 always performs better. It concluded that the performance degradation of the evaporator has larger effect on the power consumption of the compressor but the performance degradation of the condenser has an overall large effect on the COP. Miguel Padilla et.al. [5] Discuss the exergy analysis of R413A to replace R12 in domestic refrigerator by experimental. Total twelve tests performed (six tests for each refrigerant) and each test is depending on the fan velocity at condenser and evaporator. Better results obtained when fan velocity at evaporator is 0% and at condenser 100%.it gives the results that 413a gives better performance as compare to R12.
Effect of evaporator temperature
Evaporator temperature has a great effect on the performance of refrigeration system. The low quality refrigerant from expansion valve enters into evaporator where it absorbs the heat and changed into vapour. The temperature of the liquid refrigerant lower than the cooled space, therefore, refrigerant absorbs the heat. The heat transfer between the evaporator and cooled space increases with increase in evaporator temperature increases, consequently refrigerating effect increases and exergy losses decreases. V.P. Venkataramanamurthy et.al, [10] shows the comparison energy, exergy flow and second law efficiency analyses for R22, R436b in refrigeration cycles. Their result is shows that evaporating temperature has strong effects on the exergy flow losses.
Effect of condenser temperature
Condenser temperature also greatly affects the COP, second law efficiency and exergy losses. With increasing the condenser temperature, COP and second law efficiency decreases, and the exergy losses increases because the temperature differences between the condenser and outside air increases. By using the computational model Recep Yumrutas [3] shows that COP and second law efficiency increases and total exergy losses decreases with increasing the temperature of evaporator and decrease temperature of the condenser.
Refrigerant
The working fluid used in refrigeration system for heat transfer is known as refrigerant which also affect the performance of the system. There are various CFCs and HCFCs refrigerant used in many industrial and domestic applications are responsible to increase the ozone layer depletion and global warming. According to Montreal Protocol (1987) the uses of CFCs have been banned in developed countries since 1996 and in developing countries since 2010. The HCFC will be banned on European countries in 2015 and practical use limit the year 2010.Generally, R12 was used as a refrigerant in refrigerator and R22 was used in air conditioning system which has higher COP as compared to other refrigerants. But both R12 and R22 was required to replace according to the Montreal Protocol because of high ODP and GWP. M. Mohanraj [16] studies the large number of theoretical and experimental world report and give the conclusion that HC mixtures and R152a are the better substitutes to R12 in domestic refrigeration sector.R290, R1270, R290/R152a, R744 and HC/HFC mixtures are the long term substitutes for R22 in heat and in air conditioning system.
In chiller application R11, R12 and R22 can be replaced by the R123. There are the several theoretical and experimental investigation done for various alternative refrigerants can be seen in table 1
CONCLUSION
The exergy analysis shows better and accurate location of inefficiency as compared to energy analysis. Exergy losses depend on the evaporator temperature, condenser temperature, degree of sub cooling and compressor pressure. The coefficient of performance (COP) and second law efficiency increases, and exergy losses decreases with decreasing the temperature difference between the evaporator and refrigerated space and between condenser and outside air.
This means that increase in condenser temperature and decrease in evaporator temperature, result in increase the exergy losses. It is also shows that selected refrigerant should have low ODP and GWP. R134a, R-404a, R-407c, R-410a, R-290, and R152a etc. and HC refrigerants (even these are flammable) can be selected because of low ODP and GWP. From studies M. Mohanraj [16] reported that HC mixtures and R152a are the better substitutes to R12 in domestic refrigeration sector.R290, R1270, R290/R152a, R744 and HC/HFC mixtures are the long term substitutes for R22 in heat and in air conditioning system. In chiller application R11, R12 and R22 can be replaced by the R123.
ACKNOWLEDGEMENT
Authors acknowledge the immense help received from the scholars whose articles are cited and included in references of this manuscript. The authors are also grateful to authors/ editors/ publishers of all those articles journals and books from where the literature for this article has been reviewed and discussed.
References:
1. Akhilesh Arora, S.C. Kaushik, 2008. Theoretical analysis of a vapour compression refrigeration system with R502, R404A and R507A. International Journal of Refrigeration 31, 998-1005.
2. A.S. Dalkilic, S. Wongwises, 2010. A performance comparison of vapour compression refrigeration system using various alternative refrigerants. International Communications in Heat and Mass Transfer 37, 1340-1349.
3. Recep Yumrutas, Mehmet Kunduz, Mehmet Kanoglu, 2002. Exergy analysis of vapour compression refrigerations systems. Exergy, an International Journal. 2, 266-272.
4. Bilal Ahmed Qureshi, Syed M. Zubair, 2011. Performance degradation of a vapour compression refrigeration system under fouled conditions. International Journal of Refrigeration 34, 1016-1027.
5. Miguel Padilla, Remi Revelline, Jocelyn Boonjour, 2010. Exergy analysis of R413A as replacement of R12 in a domestic refrigeration system. Energy Conversion and Management 51 (2010), 2195-2201.
6. Yongmei Xuan, Guangming Chen, (2004).Experimental study on HFC-161 mixture as an alternative refrigerant to R502.
7. Arora, C.P., (2000). Refrigeration and Air Conditioning, second edition. Tata McGraw Hill publishing company limited, New Delhi.
8. Yunus A. Cengel, Michael A. Boles, (2006).Thermodynamics, Fifth edition. Tata McGraw Hill publishing company limited, New Delhi.
9. C. Nikolaidis, D. Probert, 1998. Exergymethod analysis of a two-stage vapour compression refrigeration –plants performance. Applied Energy 60, 241-256.
10. V.P. Venkataramanamurthy, Dr. Senthil Kumar, 2010. Experimental Comparative energy, exergy flow and second law efficiency analyses of R22, R436b vapour compression refrigeration cycles. International Journal of science and Technology 2(5), 1399-1412.
11. R. Llopis , E. Torrella, R Cabello, D. Sanchez, 2010. Peformance evaluation of R404A and R507A refrigerant mixtures in an experimental double stage vapours compression refrigeration plant. Applied Energy 87, 1546-1553.
12. B.O. Bolaji, Experimental study of R152a and R32 to replace R134a in a domestic refrigerator. Energy 35 (2010), 3793-3798.
13. K. Mani, V. Selladurai,2008. Experimental analysis of new refrigerant mixture as dropin replacement for CFC12 and HFC134a. International Journal of Thermal Sciences 47, 1490-1495.
14. M.A. Hammad, M.A. Alsaad, 1999. The use of hydrocarbon mixtures as refrigerants in domestic refrigerators. Applied Thermal Engineering 19, 1181-1189.
15. Vincenzo La Rocca, Giuseppe Panno, 2011. Experimental performance evaluation of a vapour compression refrigerating plant when replacing R22 with alternative refrigerants. Applied energy 88, 2809-2815.
16. M. Mohanraj, S. Jayaraj, C. Muraleedharan, 2009. Environment friendly alternatives to halogenated refrigerants-A review. International Journal of Greenhouse Gas control 3, 108-119.
17. Domkundwar &Domkundwar, (2002). Refrigeration and Air Conditioning, First edition. Dhanpat Rai & Co. (P) Ltd, New Delhi.
18. Jun Lan yang, Yi Tai Ma, Min Xia Li, Hai Qing Guan, 2005. Exergy analysis of transcritical carbon dioxide refrigeration cycle with an expander, Energy 30, 1162- 1175.
19. V. Havelsky, 2000. Investigation of refrigeration system with R12 refrigerant replacements. Applied Thermal Engineering 20, 133-140.
|